PKR Group: OLTC Analyzers (2)
Transformer OLTC diagnostic system PKR-2M
Control and diagnostics of both reactor and resistor OLTC types using non-demountable DRM mode.
the use of DRM mode for OLTC diagnostics does not require tank opening, oil draining or additional elements connection;
radial diagram measurement of the resistor and reactor type OLTCs;
resistor type OLTC contactor switchover oscillography;
simultaneous three phase control without additional external elements installation;
high-precision angular movement transducer is included to the complete set;
automatic self-adjustment to a specific OLTC;
colour-graphic, touch-screen display and PC connection through USB cable and USB-flash;
possibility of the contactor oscillogram parameter cursor measurements;
built-in measurement archive;
built-in battery (charge time: 2.5 hours);
dimensions: 360 х 290 х 165 mm, weight: 6.1 kg;
calibration period: 3 years;
Transformer OLTC diagnostic system PKR-2
Diagnostics and control of the state of OLTCs of both reactor and resistor types.
radial diagram measurement of the resistor and reactor type OLTCs;
resistor type OLTC contactor switchover oscillography;
simultaneous three phase control without additional external elements installation;
high-precision angular movement transducer is included to the complete set;
automatic self-adjustment to a specific OLTC;
colour-graphic, touch-screen display and PC connection through USB cable
possibility of the contactor oscillogram parameter cursor measurements;
built-in measurement archive;
dimensions: 360 х 290 х 165 mm, weight: 6.1 kg;
calibration period: 3 years;